IDEX Health & Science VS-606V7 Series User Manual
Page 137

137
Protective
Operation
Output is shut
OFF and motor
coasts to a
stop.
CPF-05
AD converter fault is detected
Cycle power.
If the fault remains
replace the inverter.
CPF-06
• Option card connecting
fault
• A non-corresponding option
card is connected.
Remove power to the
inverter.
Check the connection
of the digital operator.
Verify inverter software
number (n179).
CPF-07
Operator control circuit
(EEPROM or AD converter)
fault
Cycle power after
checking the digital
operator is securely
mounted.
If the fault remains,
replace the digital
operator or inverter.
Communication option card
self diagnostic error
Option card fault
Replace the option
card.
Communication option card
model code error
Communication option card
DPRAM error
OPR (Operator connecting
fault)
Cycle power.
If the fault remains,
replace the inverter.
CE (MEMOBUS
communications fault)
Check the
communication devices
or communication
signals.
Alarm Display
Inverter
Status
Explanation
Causes and
Corrective Actions
Digital
Operator
RUN (Green)
ALARM (Red)