IDEX Health & Science VS-606V7 Series User Manual
Page 155
155
First Functions (Parameters n001 to n049)
No.
Register
No. for
Trans-
mission
Name
Setting Range
Setting
Unit
Initial
Setting
User
Setting
Ref.
Page
001
0101H
Parameter write-in
prohibit / initialize
0 to 4, 6, 8, 9,
12, 13
1
1
39
002
0102
Control mode selection (Note
6)
0,1
1
0 (Note 1)
(Note 6)
40
003
0103
Operation reference
selection
0 to 3
1
0
47
004
0104
Frequency reference
selection
0 to 9
1
1
48
005
0105
Stopping method
selection
0, 1
1
0
71
006
0106
REV run prohibit
0, 1
1
0
50
007
0107
Operation stop enable/
disable selection
0, 1
1
0
70
008
0108
Frequency reference
selection
in local mode
0, 1
1
1 (Note 5)
48
009
0109
Setting method selection
for frequency reference
0, 1
1
0
48
010
010A
Detecting selection of
operator connecting fault
0, 1
1
0
47
011
010B
Maximum output
frequency
50.0 to
400.0Hz
0.1Hz
50.0Hz
40
012
010C
Maximum voltage
0.1 to 255.0V (0.2
to 510.0)
0.1V
200.0V (Note
2)
40
013
010D
Maximum voltage output
frequency
0.2 to 400.0Hz
0.1Hz
50.0Hz
40
014
010E
Mid. output frequency
0.1 to 399.9
0.1Hz
1.3Hz
40
015
010F
Mid. output frequency
voltage
0.1 to 255.0V
0.1V
12.0V
(Note 2)
40
016
0110
Minimum output
frequency
0.1 to 10.0Hz
0.1Hz
1.3Hz
40
017
0111
Minimum output
frequency voltage
0.1 to 50.0V
0.1V
12.0V
(Note 2)
40
018
0112
Accel / decel time setting
unit
0,1
1
0
55
019
0113
Acceleration time 1
0.00 to 6000s
Depend on
n018 setting
10.0s
55
020
0114
Deceleration time 1
0.00 to 6000s
Depend on
n018 setting
10.0s
55
021
0115
Acceleration time 2
0.00 to 6000s
Depend on
n018 setting
10.0s
55
022
0116
Deceleration time 2
0.00 to 6000s
Depend on
n018 setting
10.0s
55
023
0117
S-curve accel / decel
selection
0 to 3
1
0
56