Selecting Run/Stop Commands
Refer to Switching LOCAL/REMOTE Modes (Page 44) to select either the
LOCAL mode or REMOTE mode.
Operation method (RUN / STOP commands, FWD / REV run commands) can be
selected by the following method.
•
LOCAL Mode
When Lo (local mode) is selected by digital operator
ON mode, or
when the LOCAL / REMOTE switching function is set and the input terminals are
turned ON, run operation is enabled by the
or
of the digital operator,
and FWD/REV run is selected by
ON mode (using
or
key).
•
REMOTE mode
•
Select remote mode.
The following two methods are used to select remote mode:
1. Select rE (remote mode) by
selection.
2. When the local / remote switching function is selected by multi-function
input selection, turn OFF the input terminal to select remote mode.
•
Select operation method by setting the parameter n003.
n003 =0: Enables the digital operator (same with local mode)
=1: Enables the multi-function input terminal (see fig. below)
=2: Enables communications
=3: Enables communication card (optional)
•
Example for using the multi-function input terminal as operation reference
(two-wire sequence)
Below shows the example of three-wire sequence, (Refer to page 70.)
For example of three-wire sequence, refer to page 70
Note:
When inverter is operated without the digital operator, always set the
parameter n010 to 0.
)