IDEX Health & Science VS-606V7 Series User Manual
Page 62
62
•
Input / Output Open Phase Protection
*1 0% setting - no detection
*2 0.0 sec setting - no detection
•
Recommended set values: 7% for n166
10sec. for n167
5% for n168
0.2sec. for n169
Parameters
No.
Name
Unit
Setting
Range
Initial
Setting
n166
Input open-phase
detection level
1%
0 to 100% *1
400.0V/100%
(for 200V class)
800.0V/100%
(for 400V class)
0%
n167
Input open-phase
detection time
1 sec.
0 to 255 sec. *2
0 sec.
n168
Output open-phase
detection level
1%
0 to 100% *1
Inverter rated output
current value/100%
0%
n169
Output open-phase
detection time
0.1 sec.
0.0 to 2.0 sec *2
0.0 sec.