• Wire and Terminal Screw Sizes
1. Control Circuit
2. Main Circuit
200V Class 3-phase Input Series
Note:
The wire size is set for copper wires at 160
°
F (75
°
C)
Model
Terminal Symbol
Screw
Tightening
Torque
lb • in (N • m)
Wire
Applicable size
Recommend
size
Type
mm
2
AWG
mm
2
AWG
Common
to
all models
MA, MB, MC
M3
4.44 to 5.33
(0.5 to 0.6)
twisted wire 0.5 to 1.25
single
0.5 to 1.25
20 to 16
20 to 16
0.75
18
Shielded
wire or
equivalent
S1 to S7,P1, P2,SC,PC,R+,
R-,S+,S-
,FS,FR,FC,AM,AC,RP
M2
1.94 to 2.21
(0.22 to 0.25)
twisted wire 0.5 to 0.75
single
0.5 to 1.25
20 to 18
20 to 16
0.75
18
Model
Terminal Symbol
Screw
Tightening
Torque
lb • in
(N • m)
Wire
Applicable
size
Recommended
size
Type
mm
2
AWG
mm
2
AWG
CIMR-V7AA20P1
R/L1,S/L2,T/L3,-,+1,+2,B1,B2,U/T1,V/T2,W/T3
M3.5
7.1 to 8.88
(0.8 to 1.0)
0.75 to 2
18 to
14
2
14
600V
vinyl-
sheathed
wire or
equivalent
CIMR-V7AA20P2
R/L1,S/L2,T/L3,-,+1,+2,B1,B2,U/T1,V/T2,W/T3
M3.5
7.1 to 8.88
(0.8 to 1.0)
0.75 to 2
18 to
14
2
14
CIMR-V7AA20P4
R/L1,S/L2,T/L3,-,+1,+2,B1,B2,U/T1,V/T2,W/T3
M3.5
7.1 to 8.88
(0.8 to 1.0)
0.75 to 2
18 to
14
2
14
CIMR-V7AA20P7
R/L1,S/L2,T/L3,-,+1,+2,B1,B2,U/T1,V/T2,W/T3
M3.5
7.1 to 8.88
(0.8 to 1.0)
0.75 to 2
18 to
14
2
14
CIMR-V7AA21P5
R/L1,S/L2,-,+1,+2,B1,B2,U/T1,V/T2,W/T3
M4
10.65 to 13.31
(1.2 to 1.5)
2 to 5.5
14 to
10
2
14
CIMR-V7AA22P2
R/L1,S/L2,T/L3,-,+1,+2,B1,B2,U/T1,V/T2,W/T3
M4
10.65 to 13.31
(1.2 to 1.5)
2 to 5.5
14 to
10
3.5
12
CIMR-V7AA24PO
R/L1,S/L2,T/L3,-,+1,+2,B1,B2,U/T1,V/T2,W/T3
M4
10.65 to 13.31
(1.2 to 1.5)
2 to 5.5
14 to
10
5.5
10
CIMR-V7*A25P5
R/L1,S/L2,T/L3,-,+1,+2,B1,B2,U/T1,V/T2,W/T3
M5
22.19
(2.5)
5.5 to 8 10 to 8
8
8
CIMR-V7*A27P5
R/L1,S/L2,T/L3,-,+1,+2,B1,B2,U/T1,V/T2,W/T3
M5
22.19
(2.5)
5.5 to 8 10 to 8
8
8