IDEX Health & Science VS-606V7 Series User Manual
Page 65
65
Selects the function to be monitored at analog output terminals AM-AC.
In initial setting, analog voltage of approx. 10V is output when output frequency
(output current) is 100%.
Used to adjust analog output gain.
Set the analog output voltage at 100% of output frequency (output current). Frequency
meter displays 0 to 60Hz at 0 to 3V.
Using frequency meter or ammeter (n066)
Setting
Description
0
Output frequency
1
Output current
2
Main circuit DC voltage
3
Torque monitor
4
Output power
5
Output voltage reference
Calibrating frequency meter or ammeter (n067)
10V
n067 Setting
0.30
×
3V
=
Output frequency becomes
100% at this value
…