66
Analog output AM-AC can be used as a pulse train output (output frequency monitor).
Set n065 to 1 when using pulse train output.
n065 setting
Pulse train signal can be selected by setting n150.
At the factory setting the pulse of 1440Hz can be output when output frequency is
100%
Pulse monitor output can be adjusted with the parameter n067.
Using analog output (AM-AC) as a pulse train signal output (n065)
Parameters No.
Name
Unit
Setting range
Initial Setting
n065
Monitor output type selection
1
0,1
0
n065 Setting
0
Analog monitor output
1
Pulse monitor output
(Output frequency monitor)
n150 Setting
Description
0
1440Hz / Max. frequency (n011)
1
1F: Output frequency x 1
6
6F: Output frequency x 6
12
12F: Output frequency x 12
24
24F: Output frequency x 24
36
36F: Output frequency x36