IDEX Health & Science VS-606V7 Series User Manual
Page 160
160
084
0154
Jump frequency 2
0.00 to
400.0Hz
0.01Hz (less
than 100Hz) /
0.1Hz (100Hz
or more)
0.00Hz
60
085
0155
Jump frequency 3
0.00 to
400.0Hz
0.01Hz (less
than 100Hz) /
0.1Hz (100Hz
or more)
0.00Hz
60
086
0156
Jump frequency width
0.00 to
25.50Hz
0.01Hz
0.00Hz
60
087
0157
Cumulative operation
time selection (Note 9)
0.1
1
0
61
088
0158
Cumulative operation
0 to 6550
1=10H
0H
61
089
0159
DC injection braking
current
0 to 100%
1%
50%
72
090
015A
DC injection braking time
at stop
0.0 to 25.5%
0.1s
0.0s (Note 2)
72
091
015B
DC injection braking time
at start
0.0 to 25.5%
0.1s
0.0s
---
092
015C
Stall prevention (current
limit) during decel
0,1
1
0
88
093
015D
Stall prevention (current
limit) during accel
30 to 200%
1%
170%
86
094
015E
Stall prevention (current
limit) during running
30 to 200%
1%
160%
87
095
015F
Frequency detection
level
0.00 to
400.0Hz
0.01Hz (less
than 100Hz) /
0.1Hz (100Hz
or more)
0.00Hz
59
096
0160
Overtorque detection 1
0 to 4
1
0
58
097
0161
Overtorque detection 2
0.1
1
0
58
098
0162
Overtorque detection
level
30 to 200%
1%
160%
58
099
0163
Overtorque detection
time
0.1 to 10.0s
0.1s
0.1s
58
100
0164
Memory selection of hold
output frequency
0,1
1
0
77
101
0165
Speed search detection
time (Note 9)
0.1 to 10.0s
0.1s
0.2s
---
102
0166
Speed search operation
level (Note 9)
0 to 200%
1%
150%
---
103
0167
Torque compensation
gain
0.0 to 2.5
0.1
1.0
42
104
0168
Time parameter at
torque compensation
0.0 to 25.5s
0.1s
0.3s
42
105
0169
Torque compensation
iron loss
0.0 to 6550
0.01W (less
than 100W) /
1W (1000W or
more)
(Note 3)
42
106
016A
Motor rated slip
0.0 to 20.0Hz
0.1Hz
(Note 3)
44
No.
Register
No. for
Trans-
mission
Name
Setting Range
Setting
Unit
Initial
Setting
User
Setting
Ref.
Page