IDEX Health & Science VS-606V7 Series User Manual
Page 59
![background image](/manuals/545233/59/background.png)
59
Effective when either of output terminal function selections n057, n058 or n059 are set
to “frequency detection” (setting: 4 or 5). “Frequency detection” turns ON when output
frequency is higher or lower than the frequency detection level (n095).
•
Frequency detection1
Output frequency > Frequency detection level n095
(Set either of n057, n058 or n059 to “4”.)
•
Frequency detection2
Output frequency < Frequency detection level n095
(Set either of n057, n058 or n059 to “5”.)
Frequency detection (n095)