Blinking

Warning

Fault contacts
do not change
state.

OP

(parameter setting error

when the parameter setting is
performed through the
MEMOBUS communications)
OP1: Two or more values are

set for multi-function
input selection.
(parameters n050 to
n056)

OP2: Relationship among

V / f parameters is not
correct.
(parameters n011,
n013, n014, n016)

OP3: Setting value of motor

rated current exceeds
150% of inverter rated
current. (parameter
n036)

OP4: Upper/lower limit of

frequency reference is
reversed. (parameters
n033, n034)

OP5: (parameters n083 to

n085)

Check the setting
values.

Blinking

OL 3 (Over torque detection)
Motor current exceeded the
preset value in parameter
n098.

Reduce the load and
expand the accel/decel
time.

Blinking

SER (Sequence error)
Inverter receives LOCAL/
REMOTE select command or
communication/control circuit
terminal changing signals
from the multi-function
terminal while the inverter is
outputting.

Check the external
circuit (sequence).

Alarm Display

Inverter

Status

Explanation

Causes and

Corrective Actions

Digital

Operator

RUN (Green)

ALARM (Red)