There are several factors that should be considered when using relays.

Relay Life – Relays are mechanical devices that have a long but limited life. Typically, switching more
current limits the life of relays. Please check the data sheets at the end of this manual for expected relay
life.

Current / Temperature De-Rating – Products containing relays often have total current limits based on
the ambient temperature of the application. Please see the product data sheet for current / temperature
de-rating information for relays.

Fusing – External fusing is generally required to protect the relays, devices and wiring from shorts or
overloads.




























001XLE015

0V ON J1

12-24VDC

R2

C2

R3

C3

R6

C6

R4

C4

R5

C5

R1

C1

H4

H2

H3

LOAD

230VAC

OR

25VDC

N

L

LOAD

230VAC

OR

25VDC

N

L

LOAD

230VAC

OR

25VDC

N

L

LOAD

230VAC

OR

25VDC

N

L

LOAD

230VAC

OR

25VDC

N

L

LOAD

230VAC

OR

25VDC

N

L

Warning: To protect the module and associated wiring from load faults, use external (5

A)

fuse(s) as

shown. Fuses of lower current or fusing for the entire system need to be in place to assure
the maximum current rating of the unit is not exceeded.


Warning: Connecting high voltage to any I/O pin can cause high voltage to appear at other I/O pins.

Figure 10.6 – Relay Fusing