Horner APG XL6 OCS User Manual
Page 126
CH.18 MAN0883-05-EN
March 4, 2010
Page 126 of 135
#1037
18.2.2 Battery
Replacement
The XL6/XL6e OCS uses a coin lithium battery available from Horner APG.
Below are the steps to replace the battery.
1. Make sure the user program and any data stored in retentive memory is backed up.
2. Disconnect all power from the XL6/XL6e OCS unit including I/O power.
3. Remove the battery cover.
4. Note there are two connectors (X1 and X2) in the battery compartment that can accommodate
the battery connector.
5. Plug the new battery into the empty connector (X1 or X2) before removal of the old battery.
6. Remove the old battery.
7. Dispose of the old battery properly; see the above warning on disposal regulations.
8. Place the battery cover back on the unit.
9. Apply power to the unit. Check that the battery error is no longer reported. If the unit still reports
the error, remove the battery immediately and contact Technical Support.
Figure 18.1 – Back Cover - Replacing the back-up battery
Warning: Disposal of lithium batteries must be done in accordance with federal, state, and local
regulations. Be sure to consult with the appropriate regulatory agencies before disposing batteries. In
addition, do not re-charge, disassemble, heat or incinerate lithium batteries.
Warning: Do not make substitutions for the battery. Be sure to only use the authorized part number to
replace the battery.
Warning:
Lithium Batteries may explode or catch fire if mistreated
Do not recharge, disassemble, heat above 100 deg.C (212 deg.F) incinerate, or puncture.
Battery Cover