beautypg.com

Horner APG XL6 OCS User Manual

Page 123

background image

MAN0883-05-EN

CH.17

March 4, 2010

Page 123 of 135

#1037

Figure 17.5 – Cloning Status

Make/Create clone can also be triggered by setting %SR164.9 bit to “1” from Ladder program or graphics.
Once the operation is completed, this bit is made zero by the firmware. When Make clone operation is
triggered by this SR bit, it does not ask the user for confirmation for making clone. The success / failure of
the operation is also not notified on screen to the user.

In case of failure of “Make Clone” operation, %SR164.11 bit is set to “1” by the firmware and never reset.

NOTE: Backup of registers in flash memory is not performed by Clone Feature. If user desires, Backup
should be done as explained in

Chapter 16

(Fail Safe System).


17.3 Load

Clone

This option loads the application, all unit settings and register values from Removable media to the
Battery backed RAM (Regardless of AutoLoad settings) and then resets the OCS for the settings to take
effect.

User needs to perform the following to Load Clone:

1. Select “Clone Unit” from main system menu of OCS as shown below:

Figure 17.6 – System Menu