Horner APG XL6 OCS User Manual
Page 27
MAN0883-05-EN CH. 5
March 4, 2010
Page 27 of 135
#1037
5.4
RS-485 Termination
Proper RS-485 termination minimizes reflections and improves reliability.
Both serial ports allow an internal RS-485 termination resistor to be placed across pins 1 and 2 by DIP
Switch Setting.
Only the two devices physically located at the endpoints of the RS-485 network should be terminated.
5.5
RS-485 Biasing
RS-485 biasing passively asserts a line-idle state when no device is actively transmitting, which is useful
for multi-drop RS-485 networking.
Both serial ports allow internal RS-485 bias resistors to be switched in, pulling pin 1 up to 3.3V and pulling
pin 2 down to ground. The Set Serial Ports item in the System Menu can be used to enable RS-485
biasing. Also, an application graphics screen that writes to %SR164 can do the same thing. Setting
%SR164.1 enables MJ1 biasing and setting %SR164.2 enables MJ2 biasing.
If biasing is used, it should be enabled in only one of the devices attached to the RS-485 network.
5.6
Cscape Programming via Serial Port
The XL6/XL6e OCS MJ1 serial port supports CsCAN Programming Protocol, but MJ2 does not. If a PC
COM port is connected to the XL6/XL6e OCS MJ1 serial port, Cscape can access the XL6/XL6e OCS for
programming and monitoring.
5.7
Ladder-Controlled Serial Communication
Using Serial Communication function blocks, both MJ1 and MJ2 support Generic, Modbus Master and
Modbus Slave Protocols. In addition, external modems can be connected and accessed using Init, Dial
and Answer Modem function blocks.
5.8
Downloadable Serial Communication Protocols
Both MJ1 and MJ2 also support downloadable protocols, such as Allen Bradley DF1, CsCAN Master, GE
Fanuc SNP and Modbus Master.
The DIP Switches are used for
termination of the RS-485 ports. The
XL6 is shipped un-terminated.
To terminate, select one of the DIP
Switches and configure it based upon
the option that is desired.
SW1 -
ON enables MJ2 RS485 port
termination (121 Ohms).
OFF
disables
MJ2 RS485 port
termination.
SW2 & SW3 - ON places MJ2 RS485 port in
half-duplex mode.
OFF
places
MJ2 RS485 port in full-
duplex
mode.
SW4 -
ON enables MJ1 RS485 port
termination (121 Ohms).
OFF
disables
MJ1 RS485 port
termination.