beautypg.com

Horner APG XL6 OCS User Manual

Page 118

background image

CH.16 MAN0883-05-EN

March 4, 2010

Page 118 of 135

#1037

16.4 AutoLoad

This system menu option allows the user to specify whether the OCS automatically loads the application
AUTOLOAD.PGM located in Removable Media.

When the AutoLoad setting is enabled (set to YES), it can either be manually initiated or automatically
initiated at power-up.

The automatic initiation will happen only in the following two cases:

• When there is no application program in the OCS and a valid AUTOLOAD.PGM is available in the

removable media of the device.

• When the program residing in onboard memory is corrupted and a valid AUTOLOAD.PGM is

available in the removable media of the device.


AutoLoad can be manually initiated when the SYS-F3 key is pressed (OCS can be in any of the following
mode – Idle / Run / DOIO). This also requires a valid AUTOLOAD.PGM to be present in the removable
media of the device.

When the AutoLoad setting is not enabled (set to NO), OCS will be in IDLE mode and the application is
not loaded.

If the AUTOLOAD.PGM is security enabled, the user will be prompted to enter the password before
loading the application. The application will be loaded from the Removable media only after getting the
correct password.

%SR164.6 can be set to enable AutoLoad feature.

Figure 16.7 – AutoLoad Menu