3 load clone – Horner APG XL7 OCS User Manual
Page 98
![background image](/manuals/414261/98/background.png)
XL7 User Manual
4. Once the cloning is successful, OCS gives a message as below:
Figure 17.5 – Cloning Status
Make/Create clone can also be triggered by setting %SR164.9 bit to “1” from Ladder program or
graphics. Once the operation is completed, this bit is made zero by the firmware. When Make clone
operation is triggered by this SR bit, it does not ask the user for confirmation for making clone. The
success / failure of the operation is also not notified on screen to the user.
In case of failure of “Make Clone” operation, %SR164.11 bit is set to “1” by the firmware and never
reset.
NOTE: Backup of registers in flash memory is not performed by Clone Feature. If user desires, Backup
should be done as explained in Chapter 16 (Fail Safe System).
17.3 Load Clone
This option loads the application, all unit settings and register values from Removable media to the
Battery backed RAM (Regardless of AutoLoad settings) and then resets the OCS for the settings to take
effect.
User needs to perform the following to Load Clone:
1. Select “Clone Unit” from main system menu of OCS as shown below:
Figure 17.6 – System Menu