Text Tbl Size

x = Number of bytes in application text tables

Font Tbl Size

x = Number of bytes in application font tables

Protocol Size

x = Number of bytes in application downloaded protocols

SMS File Size

x = Number of bytes in application SMS protocol configuration

Firmware Rev

xx.yy = Current firmware version

OS Ver

a.b.cd.yz = Current Operating System version

FPGA Rev

x.y = Current FPGA version (High Speed IO Sub System)

InitRD Rev

x.yz = Bootloader version

Self-Test

Ok = All power-on self-tests passed

Fault = One or more power-on self-tests failed

View Diags

The View Diags Sub-Menu displays up to 11 System Diagnostics, none of which are editable.

The first two System Diagnostics are critical. If either of these indicate a Fault condition, the XL7 OCS

will not enter or remain in Run mode, and the problem must be investigated and corrected.

Logic Error:

Ok = All executed ladder instructions are legal for loaded firmware

Fault = A ladder instruction not supported by firmware was found

User Program: Ok = Ladder program and I/O configuration loaded successfully

Fault = Ladder program or I/O configuration not loaded or load failed

The last nine System Diagnostics are informational. If any of these indicate a warning condition, the XL7

OCS can still enter and remain in Run mode, but the problem should be investigated and corrected.

User Graphics

Ok = Application graphics objects loaded successfully

Fault = Application graphics objects not loaded or load failed

W-Dog Trips

0 = Watchdog timer has not tripped since the last power-up

x = Number of times watchdog timer has tripped

Net Errors

0 = No CAN network bus-off errors have occurred

x = Number of CAN network bus-off errors that have occurred

Network State

Ok = At least one other node was found on the CAN network

Warning = No other nodes were found on the CAN network

Network ID

Ok = This node’s CAN Network ID is in the range 1 to 253

Warning = This node’s CAN Network ID was out of range at power-up

Dup Net ID

Ok = This node’s Network ID is unique on the CAN network

Warning = This node’s Network ID is duplicated in another node

Clock Error

Ok = Time and date have been set

Page 55 of 110