Horner APG XL7 OCS User Manual
Page 55
![background image](/manuals/414261/55/background.png)
XL7 User Manual
Text Tbl Size
x = Number of bytes in application text tables
Font Tbl Size
x = Number of bytes in application font tables
Protocol Size
x = Number of bytes in application downloaded protocols
SMS File Size
x = Number of bytes in application SMS protocol configuration
Firmware Rev
xx.yy = Current firmware version
OS Ver
a.b.cd.yz = Current Operating System version
FPGA Rev
x.y = Current FPGA version (High Speed IO Sub System)
InitRD Rev
x.yz = Bootloader version
Self-Test
Ok = All power-on self-tests passed
Fault = One or more power-on self-tests failed
View Diags
The View Diags Sub-Menu displays up to 11 System Diagnostics, none of which are editable.
The first two System Diagnostics are critical. If either of these indicate a Fault condition, the XL7 OCS
will not enter or remain in Run mode, and the problem must be investigated and corrected.
Logic Error:
Ok = All executed ladder instructions are legal for loaded firmware
Fault = A ladder instruction not supported by firmware was found
User Program: Ok = Ladder program and I/O configuration loaded successfully
Fault = Ladder program or I/O configuration not loaded or load failed
The last nine System Diagnostics are informational. If any of these indicate a warning condition, the XL7
OCS can still enter and remain in Run mode, but the problem should be investigated and corrected.
User Graphics
Ok = Application graphics objects loaded successfully
Fault = Application graphics objects not loaded or load failed
W-Dog Trips
0 = Watchdog timer has not tripped since the last power-up
x = Number of times watchdog timer has tripped
Net Errors
0 = No CAN network bus-off errors have occurred
x = Number of CAN network bus-off errors that have occurred
Network State
Ok = At least one other node was found on the CAN network
Warning = No other nodes were found on the CAN network
Network ID
Ok = This node’s CAN Network ID is in the range 1 to 253
Warning = This node’s CAN Network ID was out of range at power-up
Dup Net ID
Ok = This node’s Network ID is unique on the CAN network
Warning = This node’s Network ID is duplicated in another node
Clock Error
Ok = Time and date have been set
Page 55 of 110