Horner APG XL7 OCS User Manual
Page 91
![background image](/manuals/414261/91/background.png)
XL7 User Manual
Restore OCS Data:
When initiated, this will allow the user to manually copy the backed up data from the onboard FLASH to
the Battery-Backed RAM.
A restore operation will be automatically initiated if a backup has been previously created and on
power-up the Battery-Backed RAM registers fail their check.
The following process will be followed for restoring data:
-
The controller will be placed in IDLE mode.
-
Data will be copied from onboard FLASH to OCS Battery-Backed RAM
-
The controller will reset.
-
The controller will be put in RUN mode if the AutoRun setting is ‘Yes’ else it will remain in IDLE
mode.
Figure 16.4 – Restore OCS Data
%SR164.3 is set to 1 only when an automatic restore operation is performed - not on a manual one. This
bit is reset to 0 when a new backup is created.
Restoring of data can be manually performed by selecting RESTORE option from the Backup / Restore
Data menu. This will cause the controller to reset.
Clear Backup Data:
When initiated, the backup data will be erased from the onboard Flash and no backup will exist.
%SR164.4 and %SR164.3 is reset to 0 when backed up data is erased.
Figure 16.5 – Clear Backup Data
Exit: Goes back to the previous screen.
Page 91 of 110