background image

XL7 User Manual

4. Configure the Ethernet Module parameters as follows:

IP Address: Enter the static IP Address for the Ethernet Module being configured.

Note: IP Addresses are entered as four numbers, each ranging from 0 to 255. These four

numbers are called octets and they are always separated by decimal points.

Net Mask: Enter the Net Mask (sometimes called Subnet Mask) being used by all nodes on the local

network. Typical local networks use Class C IP Addresses, in which case the low octet (rightmost

number) is used to uniquely identify each node on the local network. In this case, the default Net Mask

value of 255.255.255.0 should be used.

Gateway: Enter the IP Address of a Gateway Server on the local network that allows for communication

outside of the local network. To prevent the Ethernet Module from communicating outside the local

network, set the Default Gateway IP Address to 0.0.0.0 (the default setting).

Status Register: Enter an OCS Register reference (such as %R100) to indicate which 16-bit OCS register

will have the Ethernet Status word written to it. Table 7.1 shows how this register value is formatted and

explains the meaning of each bit in the Status Word.

Table 7.3 - Ethernet Status Word Register Format

High Byte

Low Byte

Bit

16

Bit

15

Bit

14

Bit

13

Bit

12

Bit

11

Bit

10

Bit 9 Bit 8 Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1

0

0

Dup Spd

0

Rx

Tx

Link

TCP Connections

Status Bit(s)

Status Indication

Status Values

Minimum

Maximum

0

Reserved

Always 0

Dup

Link Duplex (Auto-Negotiated)

0 = Half Duplex

1 = Full Duplex

Spd

Link Speed (Auto-Negotiated)

0 = 10 MHz

1 = 100 MHz

Rx

Receive State

0 = Inactive

1 = Active

Tx

Transmit State

0 = Inactive

1 = Active

Link

Link State

0 = Down

1 = Up

TCP Connections

Total Number of Active TCP Connections

(CsCAN, SRTP, Modbus, EIP, FTP, HTTP)

0

40

Version Register: Enter an OCS Register reference (such as %R101) to indicate which 16-bit OCS register

will have the Ethernet Firmware Version written to it. The value stored in the Version Register is:

(Ethernet Firmware Version * 100). For example, for Ethernet Firmware Version 4.30, the Version register

will contain 430.

Get Settings From:

“Get settings from” allows the programmer to either configure the IP Address, Net Mask, or Gateway for

2 functions: Configuration or Register