beautypg.com

Appendix “c” - troubleshooting (cont’d) – Red Lion TSC User Manual

Page 80

background image

-78-

APPENDIX “C” - TROUBLESHOOTING (Cont’d)

PROBLEMS

POSSIBLE CAUSE

REMEDIES

TEMPERATURE NOT

1. Incorrect PID values.

1. See PID CONTROL.

STABLE OR SLUGGISH

2. Heater undersized.

2. Increase heating power.

3. Improper probe location.

3. Evaluate probe location.

OUTPUTS NOT WORKING

1. Improperly wired.

1. Check wiring.

2. Incorrect output module.

2. Check output module.

3. Defective output module.

3. Check or replace output module.

LINEAR DC OUTPUT

1. Too high load resistance.

1. Check that maximum load resistance is

NOT WORKING

< 500 W (10 V).

2. Incorrect programming or scaling.

2. Check programming.

3. Connections reversed.

3. Check connections.

4. DC voltage source in loop.

4. This is an active loop. Remove all DC

voltage sources.

CONTROLLER LOCKS UP

1. Noise spikes entering controller due to load

1. a. Use Triac output module, if possible.

OR RESETS

switching transients.

b. Use RC snubbers or similar noise suppressors

at load point. (Do NOT use at the controller.)

c. Use separate AC feed line to controller.

d. Locate controller & signal lines away from

noise producing mechanisms (solenoids,

transformers, relays, etc.).

e. See “Installation Considerations Of

Electronic Instruments Controls In Industrial

Environments” in RLC catalog.

2. Defective controller.

2. Replace unit.