beautypg.com

Control points module (7-cp) 42, Con trol point set-up ( cset ) 42, Setpoint value (sp-n) 42 – Red Lion TSC User Manual

Page 44: Pid values( pid ) 42, Profiles module (8-pr) 42, Pro file set-up 42

background image

CONTROL POINTS MODULE (7-CP)

There are four Control Points, each having a setpoint value and an

associated PID gain set value. A control point can be implemented at any time

to accommodate changing process requirements due to batch changeover,

level changes, etc.

The PID gain set values (ProP, Int, & Dert) may be optionally implemented

with the setpoint value. A Control Point can be loaded from the hidden mode

or by the user input (control points 1 and 2 only, see user input control point

(CP) function).

The control point overwrites the previous setpoint and optionally the PID

values. The unit begins controlling based on these new values. When a control

point is loaded, the controller suppresses the output ‘bump’ usually associated

with PID gain changes. Control points must be manually loaded and may be

used in conjunction with a running profile.
Control Point Set-up (CSEt)

Select the control point to be configured.

NO

CP-1

CP-2

CP-3

CP-4

Selecting NO returns the unit to the configuration access point.

Setpoint Value (SP-n)

Enter the temperature setpoint value for the selected control point. This

value is constrained to the setpoint low (SPLO) and setpoint high (SPHI)

range limits (see inputs configuration module).

SP-n - -999 to 9999

PID Values(PId)

Choose the option of loading the PID gain set values with setpoint value

when implementing a Control Point.

NO - Disables PID entries and returns to control point set-up (CSEt).

YES - PID gain set is implemented when control point is loaded.

Enter the desired PID gain set values.

Pb-n - Proportional Band 0.0 to 999.9%

It-n - Integral Time 0 to 9999 secs

dt-n - Derivative Time 0 to 9999 secs

PROFILES MODULE (8-PR)

Prior to programming a profile, it is recommended to configure the basic

controller operation. A profile is a series of one or more programmable ramp

and hold phases. A minimum of three parameters are required for a profile:

Ramp Rate (Pnrn)

Target Setpoint (PnLn)

Hold Time (PnHn)

Each profile can be programmed with up to eight ramp and hold phases.

Associated with each profile is a timed event output set that updates as the

profile advances. Additional parameters are provided which enhance the

controller and profile capabilities.
Profile Set-Up

Select which profile or timed event output to program.

PSEt - Pr-1 Profile 1

Pr-2 Profile 2

Pr-3 Profile 3

Pr-4 Profile 4

PE-1 Timed event output for profile 1

PE-2 Timed event output for profile 2

PE-3 Timed event output for profile 3

PE-4 Timed event output for profile 4

The programming parameters for each profile are the same. The operator

programs each phase and continues until all eight phases are programmed or a

ramp rate of -0.1 is entered. Shown below are the parameters for profile 1.

-42-

Pr-1 - P1CC

Cycle count

P1L1

Linking

P1St

Power cycle status

P1Eb

Error band

P1r1

Ramp rate 1

P1L1

Setpoint level 1

P1H1

Hold time 1

P1r2

Ramp rate 2

P1L2

Setpoint level 2

P1H2

Hold time 2

P1r3

Ramp rate 3

P1L3

Setpoint level 3

P1H3

Hold time 3

P1r4

Ramp rate 4

P1L4

Setpoint level 4

P1H4

Hold time 4

P1r5

Ramp rate 5

P1L5

Setpoint level 5

P1H5

Hold time 5

P1r6

Ramp rate 6

P1L6

Setpoint level 6

P1H6

Hold time 6

P1r7

Ramp rate 7

P1L7

Setpoint level 7

P1H7

Hold time 7

P1r8

Ramp rate 8

P1L8

Setpoint level 8

P1H8

Hold time 8