Red Lion TSC User Manual
Page 58

Display
Parameter
Range and Units
(Factory Setting
Value)
Description/
Comments
PSEt
Setpoint Profile
NO
Pr-1
Pr-2
Pr-3
Pr-4
PE-1
PE-2
PE-3
PE-4
(NO)
NO - Return to
CNFP
Profile 1
Profile 2
Profile 3
Profile 4
Time event output
for profile 1
Time event output
for profile 2
Time event output
for profile 3
Time event output
for profile 4
The parameters for the four profiles are the same. (Pn = profile 1, 2, 3, or 4)
PnCC
Profile n
cycle count
0-250
(0)
0 = off
250 = continuous
PnLn
Profile n link option
YES/NO
(NO)
Link if more than 8
ramp/soak phases
are required.
PnSt
Profile n power-on
status
Stop- Stop profile
CONt - Continue
profile
Strt - Start profile
(Stop)
Continue has
priority.
PnEb
Profile n error band
-999 to 9999
1 or .1 degree
(0)
0 = off. (+) Values
hold phases only
(-) values ramp and
hold phases
Pnr1
Profile n ramp rate
0.0 to 999.9
degrees/minute
(0.0)
0.0 = step (instant
ramp) -0.1 ends the
profile.
PnL1
Profile n setpoint
level 1
SPLO to SPHI
1 or .1 degree
(0)
Constrained to
setpoint limit
values.
PnH1
Profile n
hold time 1
0.0 to 999.9
minutes
(0.0)
0.0 = no hold
phase.
Program up to 8 ramp/hold phases. Profile ends when ramp = -0.1 or PnH8 is programmed.
Display
Parameter
Range and Units
(Factory Setting
Value)
Description/
Comments
Pnr8
Profile n ramp rate
8
0.0 to 999.9
degrees/minute
(0.0)
Same as ramp 1.
PnL8
Profile n setpoint
level 8
SPLO to SPH
1 or .1 degree
(0)
Same as setpoint
1.
PnH8
Profile n hold time
8
0.0 to 999.9
minutes
(0.0)
Same as hold 1.
Profile returns to “PSEt” stage.
The parameters for the four timed event outputs are the same. (Pn = Timed Event
Output for proflile 1, 2, 3, or 4.)
Pn 1
Event output
number 1 for profile
n
1F2F
1F2N
1N2F
1N2N
(1F2F)
Assign alarms to
timed event output
in alarm action.
F = OFF; N = ON
1 = AL1; 2 = AL2
Each event output has the same programmable options. Event updates end when profile ends.
Pn 16
Event output
number 16, for
profile n
1F2F
1F2N
1F2F
1N2N
(1F2F)
Assign alarms to
timed event output
in alarm action.
F = OFF; N = ON
1 = AL1; 2 = AL2
Event Output step returns to “PSEt” stage.
-56-
QUICK REFERENCE TABLE: CONFIGURATION PROFILE MODULE 8 (8-PR)