Red Lion TSC User Manual

Page 55

background image

Display

Parameter

Range and Units

(Factory Setting

Value)

Description/

Comments

CYC2

Cooling output

cycle time

0 to 120 sec

(2)

0 turns OP2 off.

GAN2

Relative cooling

gain

0.0 to 10.0

(1.0)

0.0 places cooling

output into ON/OFF

control mode and

db-2 becomes

hysteresis value,

db-2

Heating/cooling

overlap-deadband

-999 to 9999

(0)

Positive value is

deadband.

Negative value is

overlap. If GAN2 =

0, this parameter is

cooling ON/OFF

control hysteresis.

-53-

QUICK REFERENCE TABLE: CONFIGURATION COOLING MODULE 5 (5-O2)

Unit returns to configuration access point if cooling option not installed.