Red Lion TSC User Manual
Page 54
Display
Parameter
Range and Units
(Factory Setting
Value)
Description/
Comments
Act1
Alarm 1 operation
mode
A-HI absolute high
A-LO absolute low
d-HI deviation high
d-LO deviation low
b-IN band inside
b-ot band outside
P-Ev timed event
output
(A-HI)
If changed, check
alarm values. If
P-Ev is selected,
remaining
parameters for
Alarm 1 does not
appear.
rSt1
Alarm 1 reset mode Auto - automatic
LAtc - manual reset
(Auto)
Manual reset via
hidden mode.
Stb1
Alarm 1 standby
function (delay)
yes/no
(no)
Power-up standby
delay
AL-1
Alarm 1 value
-999 to 9999
1 or .1 degree
(0)
If band alarm
action, positive
values only.
Act2
Alarm 2 operation
mode
A-HI absolute high
A-LO absolute low
d-HI deviation high
d-LO deviation low
b-IN band inside
b-ot band outside
P-Ev timed event
output
(A-HI)
If changed, check
alarm values. If
P-Ev is selected,
remaining
parameters for
Alarm 2 does not
appear.
rSt2
Alarm 2 reset mode Auto - automatic
LAtc - manual reset
(Auto)
Manual reset via
hidden mode.
Stb2
Alarm 2 standby
function (delay)
yes/no
(no)
Power-up standby
delay
AL-2
Alarm 2 value
-999 to 9999
1 or .1 degree
(0)
If band alarm
action, positive
values only.
AHYS
Alarm Hysteresis
value
1 to 250
1 or .1 degree
(1)
Applies to both
alarms. Set to
elimated chatter.
-52-
QUICK REFERENCE TABLE: CONFIGURATION ALARMS MODULE 4 (4-AL)
Unit returns to configuration access point if alarm(s) are not installed.