beautypg.com

Sig nal wiring 13, User in put wiring 13, Ac power wiring 13 – Red Lion TSC User Manual

Page 15

background image

Signal Wiring

When connecting the thermocouple or RTD leads, be certain that the

connections are clean and tight. If the thermocouple probe cannot be

connected directly to the controller, thermocouple wire or thermocouple

extension-grade wire must be used to extend the connection points (copper

wire will not work). Always refer to the thermocouple manufacturer’s

recommendations for mounting, temperature range, shielding, etc. For

multi-probe temperature averaging applications, two or more thermocouple

probes may be connected to the controller (always use the same type).

Paralleling a single thermocouple to more than one controller is NOT

recommended. Generally, the red wire from the thermocouple is negative and

connected to the controller’s common.

RTD sensors are used where a higher degree of accuracy and stability is

required when compared to thermocouples. Most RTD sensors available are

the three wire type. The third wire is a sense lead for canceling the effects of

lead resistance of the probe. Four wire RTD elements may be used by leaving

one of the sense leads disconnected.

Two wire RTD sensors may be used in either of two ways:

A) Install a shorting wire between terminals #8 & #9. A temperature offset

error of 2.5°C/ohm of lead resistance will exist. The error may be

compensated for by programming a temperature offset.

B) Install a copper sense wire of the same wire gage as the RTD leads. Attach

one end of the wire at the probe and the other end to terminal #8. Complete

lead wire compensation will be in effect. (preferred method)

Note: With extended cable runs, be sure the lead resistance is less than 10

ohms/lead.

User Input Wiring

The programmed User Input function is performed when terminal #7 is

used in conjunction with common (terminal #10). Any form of mechanical

switch may be connected to terminal #7. Sinking open collector logic with less

than 0.7 V saturation may also be used (no pull-up resistance is necessary).

Note: Do not tie the commons of multiple units to a single switch. Use either a

multiple pole switch for ganged operation or a single switch for each unit.

AC Power Wiring

Primary AC power is connected to the separate two position terminal block

labeled AC. To reduce the chance of noise spikes entering the AC line and

affecting the controller, a separate AC feed should be used to power the

controller. Be certain that the AC power to the controller is relatively “clean”

and within the -15%, +10% variation limit. Connecting power from heavily

loaded circuits or circuits that also power loads that cycle on and off, (contacts,

relays, motors, etc.) should be avoided.

-13-

Thermocouple Connection

RTD Connection