beautypg.com

Serial communications module (6-sc) (optional) 41, Baud rate ( baud ) 41, Par ity bit ( parb ) 41 – Red Lion TSC User Manual

Page 43: Ad dress num ber ( addr ) 41, Ab bre vi ated or full trans mis sion ( abrv ) 41, Print rate ( prat ) 41, Print op tions ( popt ) 41

background image

SERIAL COMMUNICATIONS MODULE (6-SC) (OPTIONAL)

When communicating with a TSC unit via the serial port, the data formats

of both units must be identical. A print operation occurs when the user input,

programmed for the print request function is activated, when a “P” command

is sent via the serial communications port, or after the time expires for the

automatic print rate,if enabled. Serial communication is covered in detail in

the RS-485 SERIAL COMMUNICATIONS SECTION.
Baud Rate (bAUd)

The available baud rates are:

300, 600, 1200, 2400, 4800, or 9600

Parity Bit (PArb)

Parity can be odd, even, or no parity.

Address Number (Addr)

Multiple units connected on the same RS-485 interface line must each have

a different address number. A value of 0 does not require the address specifier

command, when communicating with the TSC. The address numbers range

from 0 to 99.
Abbreviated or Full Transmission (Abrv)

When transmitting data, the TSC can be programmed to suppress the

address number, mnemonics, units, and some spaces by selecting YES. An

example of abbreviated and full transmission are shown below:

NO - 6 SET 123.8F

Full Transmission

YES - 123.8

Abbreviated Transmission

Print Rate (PrAt)

The TSC can be programmed to automatically transmit the selected print

options at the programmed print rate. Selecting 0 disables the automatic print

rate feature.

PrAt - 0 to 9999 seconds

Print Options (PoPt)

Selecting YES for the print options will allow the operator to scroll through

the available options using the PAR button. The up and down arrow keys

toggle between “yes” and “no” with “yes” enabling the option to be printed

when a print function occurs.

INP

Print Input Temperature Value

SEt

Print Setpoint Value

OPr

Print % Output Power Value

Pdb

Print % Proportional Band Value

INt

Print Integral Time Value

dEr

Print Derivative Time Value

AL1

Print Alarm 1 Value

AL2

Print Alarm 2 Value

dEv

Print Deviation From Setpoint Value

OFP

Print % Output Power Offset Value

r-P

Print Setpoint Ramp Rate Value

CrG

Print Cooling Relative Gain Value

Cdb

Print Cooling Deadband Value

P-t

Print Profile Phase Time Remaining

P-S

Print Profile Operation Status

-41-