If more than one string is transmitted, there is a 100 msec minimum to 200
msec maximum built-in time delay after each transmission string and after
each block of transmission. When interfacing to a printer, sending mnemonics
are usually desirable. Examples of transmissions are shown below:
1 TMP 500F
Mnemonics Sent
1 SET 525F
1 PWR 20%
-673.5
NO Mnemonics Sent
The Print Options provide a choice of which TSC data values are to be
transmitted. The TSC will transmit the Print Options when either the User
Input, programmed for the print request function is activated, a “P” (Transmit
Print Options) command is sent to the TSC via the serial port, or the Automatic
Print Rate is set for a specific time. The Print Options are programmed in the
Serial Communications Module (6-SC) with the available options:
1. Print Display Temperature Value.
2. Print Setpoint Value.
3. Print % Output Power Value.
4. Print % Proportional Band Value.
5. Print Integral Time Value.
6. Print Derivative Time Value.
7. Print Alarm 1 Value.
8. Print Alarm 2 Value.
9. Print Deviation From Setpoint Value.
10. Print % Output Power Offset Value.
11. Print Setpoint Ramp Rate Value.
12. Print Cooling Relative Gain Value.
13. Print Cooling Deadband Value.
14. Print Profile Phase Time Remaining.
15. Print Profile Status.
A print out from a TSC unit with an address of 1 and all print options
selected is shown below:
1 TMP
500F
1 SET
525F
1 PWR
20.0%
1 PBD
4.0%
1 INT
120S
1 DER
30S
1 AL1
600F
1 AL2
475F
1 DEV
-25F
1 OFP
0.0%
1 RMP
0.0R
1 CRG
1.0G
1 CDB
10F
1 TIM
1.6M
1 STS
P2H3
Note: If the cooling option is installed, AL2 is not printed or functional.