beautypg.com

Red Lion TSC User Manual

Page 63

background image

If more than one string is transmitted, there is a 100 msec minimum to 200

msec maximum built-in time delay after each transmission string and after

each block of transmission. When interfacing to a printer, sending mnemonics

are usually desirable. Examples of transmissions are shown below:

1 TMP 500F100 - 200 msec

Mnemonics Sent

1 SET 525F100 - 200 msec

1 PWR 20%100 - 200 msec

-673.5100 - 200 msec

NO Mnemonics Sent

The Print Options provide a choice of which TSC data values are to be

transmitted. The TSC will transmit the Print Options when either the User

Input, programmed for the print request function is activated, a “P” (Transmit

Print Options) command is sent to the TSC via the serial port, or the Automatic

Print Rate is set for a specific time. The Print Options are programmed in the

Serial Communications Module (6-SC) with the available options:

1. Print Display Temperature Value.

2. Print Setpoint Value.

3. Print % Output Power Value.

4. Print % Proportional Band Value.

5. Print Integral Time Value.

6. Print Derivative Time Value.

7. Print Alarm 1 Value.

8. Print Alarm 2 Value.

9. Print Deviation From Setpoint Value.

10. Print % Output Power Offset Value.

11. Print Setpoint Ramp Rate Value.

12. Print Cooling Relative Gain Value.

13. Print Cooling Deadband Value.

14. Print Profile Phase Time Remaining.

15. Print Profile Status.

A print out from a TSC unit with an address of 1 and all print options

selected is shown below:

1 TMP

500F

1 SET

525F

1 PWR

20.0%

1 PBD

4.0%

1 INT

120S

1 DER

30S

1 AL1

600F

1 AL2

475F

1 DEV

-25F

1 OFP

0.0%

1 RMP

0.0R

1 CRG

1.0G

1 CDB

10F

1 TIM

1.6M

1 STS

P2H3

Note: If the cooling option is installed, AL2 is not printed or functional.

-61-