beautypg.com

Using display/keypad, Figure 45, Alarm limits shown on graph screen – Vaisala PTU300 User Manual

Page 79: Figure 46, Display alarm active

background image

Chapter 4 _________________________________________________________________ Operation

VAISALA ________________________________________________________________________ 77

- To have the alarm activate when the measured quantity is inside the

range, set the Act. above limit lower than the Act. below limit.

The alarm limits are shown on the graph display as thicker dotted lines.
When a display alarm is activated, the automatic scaling of the graph
display always keeps the limits in view.

1102-012

Figure 45

Alarm Limits Shown on Graph Screen

When an alarm is activated, an alarm note is displayed on the display,
and the lights of the display will blink. If the data logger module is
installed, the alarm note includes the time and date of the alarm.

0802-041

Figure 46

Display Alarm Active

Multiple alarms can be active at the same time; the alarm that was
triggered first will be shown on the display. The next active alarm is
revealed when the currently shown alarm is acknowledged by pressing
the OK button.

Activated alarms are only shown on the screen; there are no alarm
messages output to the serial line. After an alarm has been
acknowledged, you must refer to the data graphs to see when the
measured quantities have exceeded the limits. You may use the optional
relay outputs as alarm outputs by configuring them separately; see
section Setting Relay Outputs on page 137.

Using Display/Keypad

1.

Enter the Main Menu by pressing an arrow button on the keypad.

2.

Use the arrow keys to select Display, followed by Alarms, to open
the Display Alarms menu. The Display Alarms menu shows the
currently enabled and disabled alarms.