Appendix C _________________________________________________________ Modbus Reference
VAISALA _______________________________________________________________________ 211
Status Registers (Read-Only)
Table 46
Status Registers
Name
Address
Description
Fault status
0513
1 = No errors
Online status
0514
1 = Online data available
Pressure stability
0515
1 = OK
Error code (bits 15…0)
0516
Bit field that represents the
error codes listed in Table 36
on page 158. Active errors are
set to 1. For example, if bit 14
is set to 1, error code E14 is
active.
Error code (bits 31…16)
0517
Error information can retrieved also with function code 08, sub-function
02.
NOTE
Basic status information of the PTU300 transmitter is also available with
the Read Exception Status function code 07. For details, see section
Exception Status Outputs on page 212.
Configuration Registers
Configuration parameter registers are used to configure the measurement.
Writing out-of-range values is silently ignored.
Table 47
Configuration Parameter Registers
Name
Float
Integer
Valid Range
Pressure setting default
value
0769…0770
1025 (×1)
0…9999 hPa
Pressure setting
temporary value
0771…0772
1026 (×1)
0…9999 hPa
Chemical purge interval 0773…0774
1027 (×1)
10…2880 min
Molecular weight for
ppm
w
calculation
0775…0776
1028 (×0.001)
0…999.999
g/mol
QNH height
0781…0782
1031 (×0.1)
-30…3000 m
QFE height
0783…0784
1032 (×0.1)
±30 m
HCP height
0785…0786
1033 (×0.1)
±30 m
Maximum pressure
change
0787…0788
1034 (×0.01)
0…10 hPa
Maximum pressure
difference
0789…0790
1035 (×0.01)
0…10 hPa
If you modify the pressure setting repeatedly, modify the temporary
value at register 0771...0772 (1026) instead of the permanent setting at
register 0769…0770 (1025). Set the temporary value to zero to return to
the default pressure setting.