3
3.11 "Clear" Control Function
The "Clear" operation is accessible from the following commands; "Clear" command executed via the "Clear"
switch, RSH "Clear" Command, PNS "Clear" command, SNMP "Clear" Command, or a "Clear" Command
from the Web Setup Tool.
Refer to "4.12 "Clear' Control Setup Screen" for details on the setting method.
3.12 Normal Mode Settings
The Signal Tower can be set up to display its "normal state of operation", based on the user's preference for
lights and buzzers to be on when no warning conditions occur. Refer to "4.13 Normal Mode Setup Screen" for
details on setting it up via the Web Setup Tool.
3.13 Reinitialization Function
From the Web Setup Tool, this unit can be reinitialized to revert all settings back to the default (factory)
settings, while leaving the network settings as is when resetting the other settings. Refer to "4.16
Reinitialization Setup Screen" for details on the setting method.
Also, it can initialize the network settings of this product to its default settings in addition to returning the other
settings to their default settings.
【Method for full initialization, including the network setup】
1. Set the volume level switch to the "HIGH" position.
2. Turn on the power supply while simultaneously pushing the "TEST" switch.
3. After the Signal Tower does an all-point lighting test, the Signal Tower lights go out. Release the switch
after all the Signal-Tower lights are out.
4. The Signal Tower will light up again about 1 minute after. The Signal Tower will then flash Pattern1
afterward to indicate the initialization is complete.
5. Push the clear button to stop the flashing.
※ If the Ping monitor etc. are set up, an abnormal operation detection may occur.
【Method for initialization to revert the network settings back to the factory default value】
1. Set the volume level switch to the "OFF" position.
2. Turn on the power supply while simultaneously pushing the "CLEAR" and "TEST" switch.
3. After the Signal Tower does an all-point lighting test, the buzzer will make an audible sound. Release the
switch after the buzzer sounds.
4. When the Signal Tower goes out, it indicates the completion of initilization.
3.14 Event Log Output Function
The Web Setup Tool displays an event log. Moreover, it is possible to download it as a text file. The following
is the description of the recording mode labels for the event log.
Event Name
coldStart
Event Contents
No Display
Event Details
Records at the moment of start up.
Event Name
ACCESS
Event Contents
No Display
Event Details
Records at the moment of authentication failure.
Records at the moment of Web login failure.
Event Name
Event Contents
E-mail Transmission
Event Details
Records at the moment of an e-mail transmission.
Please
Do not overexert pressure to the "CLEAR" switch, "TEST" switch and volume level switch. Failure