7 e-mail sending function, 1 e-mail message contents – PATLITE NHL User Manual
Page 29
29
3
3.7 E-mail Sending Function
It can transmit up to eight registered e-mail addresses. The subject and message of the transmitting mail
can be registered for 16 different situations per subject title to be transmitted via e-mail to the 8 registered
addresses. The user authentication method during transmission can be selected from either "SMTP
Authentication", "POP Authentication", or "No Authentication". Refer to "4.6 E-mail Sending Setup Screen"
and "4.7 E-mail Message Setup Screen" for further details of the setting method.
3.7.1 E-mail Message Contents
The registration of 16 subjects and 16 messages for transmitting mail can be selected in combination when
sending an alert message of up to 8 registered E-mail addresses. The e-mail text would include the equip-
ment name, its location, the sender, the message, and supplementary information indicated in table 3.7.1 be-
low. The contents of the registered subject is indicated.
If the 17th fixed e-mail subject title “NH-ORIGINAL” is selected, the equipment location, message transmis-
sion time stamp, and event contents is indicated. If the 17th e-mail subject text is selected as “None”, nothing
is indicated in the text.
[Registered subject title when selecting No. 17 is "NH-ORIGINAL"]
System Location: YY/MM/DD hh:mm Contents of the event: Name
Table 3.7.1 Fixed Written Subject Contents
Generated Event
Indicated Event Contents
Indicated Name
TRAP Reception
Blank
TRAP Monitor Setup Registered Group Name
Execute "Clear" by pushbutton
“: CLEAR-Switch”
Blank
Execute "Clear SNMP"
“: CLEAR-SNMP”
Blank
Execute "Clear RSH"
“: CLEAR-RSH”
Blank
Ping Monitor Abnormality Detection
“: PING-Error”
The equipment name registered in the Ping Monitor
setup
Ping Monitor Recovery Detection
“: PING-Recover”
The equipment name registered in the Ping Monitor
setup
Application Monitor Abnormality
Detection
“: APP-Error”
The equipment name registered in the Application
Monitor setup
Application Monitor Recovery
Detection
“: APP-Recover”
The equipment name registered in the Application
Monitor setup
Execute “Clear RSH Command”
“: RSH-Executes”
Blank
“TEST” button pressed
“: TEST-Switch”
Blank