• Example 3: Reset if the Pulse Sum Exceeds a Set Value

If the pulse sum exceeds a set value (the reset value), reset the sum and carry over

the value that exceeds the reset value. Count the number of resets, and calculate the
total pulse sum.

Calculation Expression

This table shows which calculation expressions to assign to which channels and what

constants to set.

Channel

Calculation Expression

Description

101

((102+P01).GE.K01)+101

Number of pulse sum resets

102

CARRY(K01):TLOG.SUM(P01)

Pulse sum

103

K01*101+102

The total pulse sum

Variable

Description

P01

The number of pulses per scan interval.

K01

A constant. The reset value. Values that exceed it are reset.

0

0

1

1

1

2

2

P01

Number of pulses

per scan interval

102ch

Sum value

101ch

Reset count

Pulse input

Scan interval

Time

K01

Reset value

(Resets the value below the reset value)

(Sum)

Channel 101: Reset Count

Calculates the number of pulse sum resets.
((102+P01).GE.K01) returns a value of 1 when the value of the previous pulse sum

(102) + the current pulse count (P01) is greater than or equal to the reset value
(K01). Otherwise, it returns a value of zero. The value of Channel 101 increases by 1
whenever the pulse sum exceeds the reset value.

Channel 102: Pulse Sum

Calculates the pulse sum.
This channel normally calculates the pulse sum, TLOG.SUM(P01). If the pulse sum

goes above the reset value (K01), the excess value is set as the new pulse sum.

Channel 103: Total Pulse Sum

This channel multiplies the reset value (K01) by the reset count (101) and adds the

pulse sum (102) to get the total pulse sum.

Note

• Computation starts with the smallest channel number at every scan interval. If a channel

number in a calculation expression is greater than or equal to the number of the channel
that contains the expression, the previous computed result (the previous value) of the
channel with that number will be used in the expression.

• Because the computation function uses single-precision floating-point representation, we

recommend that you set the reset value below 10

7

.

• The MV will not compute values correctly if the pulse input value of a scan interval is larger

than the reset value.