Code
Message
Explanation/Countermeasures/Ref. section
102
SUBNET mask is incorrect.
Check the subnet mask.
Section 2.2 in the communication manual
103
The net part of default gateway is not equal to that of IP
address.
Check the IP address.
Section 2.2 in the communication manual
105
This port number is already in use. Please enter a different
number.
Enter a different port number for each function.
Section 7.1 in the communication manual
113
Password entered is incorrect.
Enter the correct password.
See section 8.3
119
This user name is unable to use this mode.
A user-level user cannot enter the Basic Setting
mode.
See section 8.2
120
Measured value is incorrect. (in ascending order)
Set the calibration correction value to a value greater
than the previous value.
See section 3.9
122
Measured value exceeds the range setting.
Check the channel input or the channel range setting.
See sections 3.3 and 3.9
125
Character entry cannot be performed.
The MV is not showing a display used to enter
character strings.
See section 9.7
126
You cannot use the same password.
Specify a different password.
See section 8.3
127
Report kind overlaps and cannot be set up.
Change the overlapped report data type.
See section 10.5
129
IP address is not set.
Set the MV IP address.
Section 2.2 in the communication manual
131
You have exceeded the available channel capacity.
You cannot connect more than 240 channels.
Section 2.9 in the communication manual
132
You have exceeded the available number of commands.
The maximum number of commands that can be
sent is 16. The modules that can be set with a
single command are consecutive modules that can
be automatically set. Change the MW100 module
configuration so that there are no empty slots.
Section 2.9 in the communication manual
133
External I/O auto setting information is not available.
Below are the possible causes. Check them.
• The MW100 is in calibration mode. Change to the
setting mode or measurement mode.
• The measurement module may not have been
detected. Perform system reconfiguration.
• There are no modules that can be automatically set.
Check the modules.
• An IP address has not been assigned to the
MW100. Set the IP address.
• The Modbus server of the MW100 is turned OFF.
Turn the server ON.
Section 2.9 in the communication manual
134
Auto setting has already been executed.
You cannot set an MW100 that has been
automatically set.
Section 2.9 in the communication manual
135
External I/O cannot be found.
Check the Ethernet connection.
Section 2.2 in the communication manual
136
External I/O start cannot be executed.
The current MW100 settings do not allow the
measurement to be started. Check the settings.
137
DNS for this device is not set.
Set the MV DNS parameter.
Section 2.2 in the communication manual
12.1 List of Messages