beautypg.com

3 storage function, Configuration, Data types – Yokogawa Button Operated MV2000 User Manual

Page 268: Display data and event data

background image

13-6

M-4660

13.3 Storage Function

Configuration

Item

Specifications

Internal memory

Temporarily stores various types of data

Medium

Flash memory

External storage medium

Medium

CF card (up to 2 GB)

Format

FAT32 or FAT16

Data Types

Data Type

Extension

Format

Display Method
MV

DAQSTANDARD

Application

Display data

DAD

Binary (undisclosed)

Yes

Yes

Yes

1, 2

TDD

Text

-

-

Yes

Event data

DAE

Binary (undisclosed)

Yes

Yes

Yes

1, 2

TDE

Text

-

-

Yes

Report data

DAR

Text

Yes

Yes

Yes

Manually sampled data

DAM

Text

-

-

Yes

Setup data

PDL

Binary (undisclosed)

Yes

Yes

-

Snapshot data

PNG

PNG (general format)

-

-

Yes

1 You can convert the data format on DAQSTANDARD and then open the data on a software application such as Microsoft Excel.
2 You can open on a software application, the data loaded from the MV through the communication function.

Display Data and Event Data

Item

Specifications

Internal memory

File storage capacity

80 MB (standard memory) or 200 MB (large memory)

Number of files

Up to 400

Operation

FIFO (First In First Out)

Display data

Source

Measurement, computation, and external input channels (/MC1)

Sampling interval

Set by Trend/Storage interval
RD-MV1004, RD-MV1008, RD-MV2008: Select from 5 s, 10 s, 15 s, 30 s, 1 min, 2 min, 5 min, 10
min, 15 min, 20 min, 30 min, 1 h, 2 h, 4 h, 10 h/div
RD-MV1006, RD-MV1012, RD-MV1024, RD-MV2010, RD-MV2020, RD-MV2030, RD-MV2040, RD-
MV2048: Select from 15 s (only for fast sampling mode), 30 s, 1 min, 2 min, 5 min, 10 min, 15 min, 20
min, 30 min, 1 h, 2 h, 4 h, 10 h/div

Contents

The maximum and minimum values within the data update interval among the data values
sampled at the scan interval

Data size

Measurement and external input channel (/MC1) data: 4 bytes/data value. Computation channel
data: 8 bytes/data value.

Files size

Up to 8 MB

Data format

Binary or text

Recording

Records data at all times

Event data

Source

Measurement, computation, and external input channels (/MC1)

Sampling interval

Set by Sample rate
Select from 25ms, 125ms, 250ms, 500ms, 1s, 2s, 5s, 10s, 30s, 1min, 2min, 5min, and 10min
However, you can only set rates that are slower than the scan interval.

Contents

Data for each sampling interval

Data size

Measurement and external input channel (/MC1) data: 2 bytes/data value. Computation channel
data: 4 bytes/data value.

Files size

Up to 8 MB

Data format

Binary or text

Mode

Free: Records data at all times
Triggered: Starts recording data when a certain event occurs and stops after a specified interval.

Saved data combinations

Display data only, event data only, or display data and event data.

File size

See appendix 1.

This manual is related to the following products: