beautypg.com

Yokogawa Button Operated MV2000 User Manual

Page 285

background image

App-2

M-4660

• Sampled Data Size per File
Display Data
Data size per sample×file save interval/sampling interval
The sampling interval is determined by dividing the Trend/Storage interval (s/div) by

30.

Example 2: When recording the display data of 30 measurement channels, 240

external input channels, and 10 computation channels with the Trend/
Storage interval set to 30 min/div (display data sampling interval is 60 s)
and the file save interval set to 1 day (24 h)

(30×4 bytes + 240×4 bytes + 10×8 bytes + 8 bytes)×24hЧ60Ч60/60 s
= 1,168 bytes×24hЧ60Ч60/60 s
= 1,681,920 bytes

Event Data

Data size per sample×data length/sample rate

Example 3: When recording the event data of 30 measurement channels, 240

external input channels, and 10 computation channels with the sample
rate set to 1 s and the data length set to 2 h.

(30×2 bytes + 240×2 bytes + 10×4 bytes + 8 bytes)×2hЧ60Ч60

/

1 s

= 588 bytes×2hЧ60Ч60/1 s
= 4,233,600 bytes

Size of a File

The size of a file is the sum of the sampled-data related information size and the sampled
data size.
Display Data
Example 4: When recording under the conditions given in examples 1 and 2
From examples 1 and 2, the size of a file is 36,842 + 1,681,920 = 1,718,762 bytes ≈

1.639 MB.

Event Data
Example 5: When recording under the conditions in examples 1 and 3
From examples 1 and 3, the size of a file is 36,842 + 4,233,600 = 4,270,442 bytes ≈

4.073 MB.

Appendix 1 Data File Size

This manual is related to the following products: