App

Index

File Output Example

Below is an example of manually sampled data for channels 1, 2, 3, and 4.

YREC
Manual Sample Data

Version 1.00.00

Model

RD-MV2000

Language Code

shift-JIS

File Status

Progress

Serial No.

S5E701600

File Header
Ch

CH001

CH002

CH003

CH004

Tag

TI-101

OUT-102

FI-103

VA-204

Unit

˚C

V

m3/h

%

2008/01/23 08:57:22 213.8

0.517

368.4

68.9

2008/01/23 08:57:28 208.6

0.494

363.0

68.1

Note

• The output when error data, range-out data, or computation range-out data is detected

Channel

Data

Output

Measurement
channels and

Error

(Space)

external input
channels

Positive range-out (includes burnout detection)

99999

Negative range-out (includes burnout detection)

–99999

Computation
channels

Error

999999999

Positive computation range-out (when the value
exceeds approx. 3.4E+38)

999999999

Negative computation range-out (when the value is
less than approx. –3.4E+38)

–999999999

• The MV generates a new manually sampled data file in the following cases:

• A measurement channel is changed to Skip from a range other than Skip.
• A measurement channel is changed from Skip to a range other than Skip.
• A computation or external input channel is changed from On to Off or Off to On.
• The unit is changed.

Appendix 3 Text File Formats