beautypg.com

1 setting a display group – Yokogawa Button Operated MV2000 User Manual

Page 149

background image

6-1

M-4660

Display Configuration

1

2

3

4

5

6

7

8

9

10

11

12

13

App

Index

Chapter 6

Display Configuration

6.1

Setting a Display Group

This section explains how to assign channels to a display group and how to name the
group. It also explains how to set lines at specified positions in the waveform display
range on the trend display.

Display

Press MENU and then select Menu tab > Group set, Trip line.

Settings

• Group number

Select the target group number (from 1 to 10 on the RD-MV1000 and 1 to 36 on the

RD-MV2000).

• Group set
• On/Off

Select On to use the group.

• Group name

Set the group name (up to 16 characters,

A a # 1

).

• CH set

Select measurement channels, computation channels (/M1 and /PM1 options), and

external input channels (/MC1 option) that you want to assign to the group. You
can set up to 6 channels on the RD-MV1000 and up to 10 channels on the RD-
MV2000.

• Enter channel numbers using two or three digits.
• Separate each channel number with a period.
• To specify a range of consecutive channels numbers, use a hyphen.
Example: To assign channel 1 and channels 5 through 8, enter “001.005-008.”

Note

• The MV displays the channels in the specified order on the trend, digital, and bar graph

displays.

• You can assign a channel to multiple groups.
• You cannot assign a channel twice to the same group.