3.5 Setting the Auxiliary Alarm Function

An example of the relay action when AlarmACK is executed is shown below. This

example is for the case when the output relay AND item is set to None.

Normal

Alarm ACK

Alarm output relay

Alarm 2

Alarm 1

Relay is activated at the next scan interval

Activated

Alarm

occurrence

Alarm

occurrence

Deactivated

Reset

Alarm ACK

Relay is activated on the next alarm occurrence

Alarm output relay

Alarm 2

Alarm 1

Activated

Alarm

occurrence

Alarm

occurrence

Deactivated

• Hysteresis > Meas CH
• High/Low

The hysteresis width for alarm occurrence/release of the high/low limit alarm that is

set for measurement channels.

Selectable range: 0.0% to 5.0% of the span or scaling width.

• Delta High/Low

The hysteresis width for alarm occurrence/release of the difference high/low limit

alarm that is set for measurement channels.

Selectable range: 0.0% to 5.0% of the span.

• Hysteresis > Math CH (/M1 and /PM1 options), Ext. CH (/MC1 option)

The hysteresis width for the alarm occurrence/release of the high/low limit alarm that

is set for computation channels and external input channels.

Selectable range: 0.0% to 5.0% of the measurement span.