Device Status Output

The following status notifications are output with a relay contact signal. You can choose
whether or not to output each kind of status notification. The relay is energized when the
status occurs. This cannot be changed.

For configuration instructions, see section 9.6.

Status

Description

Corrective Action

Status of the internal
memory or CF card

Internal memory error.

Contact your nearest Omega
dealer for repairs.

When the auto save to the CF card function is On.

• The free space on the CF card has

dropped to 10% of the total size.
(only when FIFO is disabled. For
details on FIFO, see section 1.5.)

Replace the CF card.

• CF card error.

• Replace the CF card.
• Use the MV to format the CF

card (the CF card data will
be deleted).

However, the status of the internal
memory is output when the CF card
is not inserted.
• 10 MB or less of available space

*

remaining in internal memory.

• The number of files in internal

memory for which Auto Save to the
CF card has not been completed
has exceeded 390.

Insert a CF card.

When the auto save to the CF card function is Off.

• 10 MB or less of available space

*

remaining in internal memory.

• The number of files in internal

memory that have not been
manually saved has exceeded
390.

Save the data in the internal
memory to the CF card.

Measurement error

A/D converter error.

Contact your nearest Omega
dealer for repairs.

Burnout detected.

Replace the thermocouple
that has burned out.

Communication error Modbus master or Modbus client

communication error.

Check the error by using the
Modbus master or Modbus
client display and perform
corrective actions.

FTP file transmission error.

Check the FTP log and
perform corrective actions.

Memory stop

Memory sampling has stopped.

Start memory sampling.

* The internal memory’s “available space” refers to the following areas:

• Unused areas of internal memory

• Data areas for which Auto Save or Manual Save (see section 1.5 for details) has been

completed.

Relay Operation

NO

C

NC

During normal

operation

NO

C

NC

When specified

status occurs

NO

C

NC

When power is

turned OFF

1.10 FAIL/Status Output Function (/F1 option)