beautypg.com

App index, Actions – Yokogawa Button Operated MV2000 User Manual

Page 44

background image

1-37

M-4660

Feature Overview

1

2

3

4

5

6

7

8

9

10

11

12

13

App

Index

• Match Time Timer

You can set four match time timers. Specify the date/time using the method described

below. For each timer, you can select whether to use the timer once or continuously.
The timers are also used with the TLOG computation function (/M1 and /PM1 options).

Specified Date/Time

Description

Month, day, hour

Occurs once a year.

Day and hour

Occurs once a month.

Day of the week and hour

Occurs once a week.

Hour

Occurs once a day.

Actions

• List of Actions

You can choose from the following actions.

Action

Level/Edge*

Description

MemoryStart/Stop

Level

Starts or stop memory sampling.

MemoryStart

Edge

Starts memory sampling.

MemoryStop

Edge

Stops memory sampling.

Trigger

Edge

Triggers the recording of event data. Valid
when recording event data in a triggered
mode. See the next page for more details.

AlarmACK

Edge

Stops alarm output.
Valid when the MV is configured to use the
alarm output release (AlarmACK) operation.

MathStart/Stop**

Level

Starts or stops computation.

MathStart**

Edge

Starts computation.

MathStop**

Edge

Stops computation.

MathReset**

Edge

Resets the values on all computation
channels.

SaveDisplay

Edge

Saves the display data currently being
recorded to internal memory. This is the
same as saving data by pressing FUNC.

SaveEvent

Edge

Saves the event data currently being
recorded to internal memory. This is the
same as saving data by pressing FUNC.

Message

Edge

Writes a message.
Can be executed during memory sampling.

Snapshot

Edge

Saves an image of the screen.

DisplayRate1/2

Level

Switches between the first and second trend
update intervals.
Valid when the MV is set to be able to switch
between trend intervals.

ManualSample

Edge

Executes manual sampling.

TimerReset

Edge

Resets the relative timer. Timing begins
again from the point where the timer is reset.
See the next page for more details.

DisplayGroupChange

Edge

Changes the display group in the trend,
digital, or bar graph display.

Flag**

Level

0 (normal) or 1 (when an event occurs).
Flags can be used in computation channel
expressions.

PanelLoad

Edge

Reads the setup data file in the root directory
of the CF card and uses it to configure the
MV. See the next page for more details.

TimeAdjust

Edge

Sets the time to the closest hour. See the
next page for more details.

* For a description of level and edge, see “Miscellaneous” in this section.
**This is an option.

1.7 Event Action Function

This manual is related to the following products: