Cycle time, output 1a or 2a, Dead band a, Ct1a] [ct2a] [db`a – Watlow Series 998 User Manual
Page 80: Operation-pid a
5.12
WATLOW Series 998 User’s Manual
Operation Menus, Chapter 5
Operation-PID A
Cycle Time, Output 1A or 2A
Select the time, in seconds, of a complete on/off cycle.
[Ct1A] This prompt does not appear if the output is a process output or
[Pb1A] is not set higher than [```0].
If
Default
↓
↓
mechanical
[``%0]
…
[`1)0]
…
[99(9]
min.
relay
[Ct1A]
[Ct1A]
[Ct1A]
outputs
open collector
[brSt]
…
[``!0]
…
[99(9]
min.
or solid-state
[Ct1A]
[Ct1A]
[Ct1A]
relay outputs
Dead Band A
Select the width of the zone between the action of the channel A
heating output and cooling output. If you select a positive value the
heat and cool outputs cannot be energized at the same time. If you select
a negative value, both outputs can be energized at the same time.
• If a process input is selected, the decimal precision will be determined by
the [dEC1] setting (Input Menu).
[db`A] This prompt appears only if [Pb1A] and [Pb2A] are set higher than
[```0] and one channel A output performs heating action and the other
performs cooling action.
If
Default
↓
↓
[``°F]
[-999]
…
[```0]
…
[`999]
[`C_F]
[db`A]
[db`A]
[db`A]
(Global Menu)
[``°C]
[-555]
…
[```0]
…
[`555]
[`C_F]
[db`A]
[db`A]
[db`A]
(Global Menu)
a process
[-999]
…
[```0]
…
[`999]
units
input is selected
[db`A]
[db`A]
[db`A]
[Ct1A]
[Ct2A]
[db`A]