beautypg.com

Auto-tuning, Auto-tuning (heat and/or cool) – Watlow Series 998 User Manual

Page 103

background image

WATLOW Series 998 User’s Manual

7.1

Tuning, Alarms and Error Codes, Chapter 7

Auto-tuning (Heat and/or Cool)

The Series 998 can automatically tune the PID parameters for both
channel A and channel B to fit the characteristics of your particular sys-
tem. Only one channel’s PID set can be auto-tuned at a time.

Before beginning the auto-tune sequence, make sure the [AtSP] parame-
ter located in the Global Menu is at the proper setting. This allows the
user to select the tuning set point as a percentage of the current control
set point. See Chapter 4 for more information on this parameter. The fig-
ure below uses the 90% default setting to define the auto-tuning process.

Once the auto-tune sequence has begun, the control outputs proportional
band for the associated channel is set to 0 and that channel goes into an
on/off mode of control at the channel’s set point percentage determined
by the [AtSP] parameter. The channel’s displayed set point remains
unchanged. Note: Any change in the set point while in auto-tune restarts
the auto-tune procedure.

Once the control finishes “learning” the system, it returns the channel to
standard PID control with the PID values automatically set as a result of
auto-tuning.

Once auto-tune has begun, the process must cross the set point four
times within 80 minutes for the 998 to successfully complete the auto-
tune. If this does not happen within the time limit, the Series 998 chooses
PID values based on the 80-minute tuning cycle performed.

Figure 7.1 -
Auto-tuning
Example.

200

°

Temp

Set Point

100

°

Process

180

°

Auto-tune

Begins

Auto-tune
Complete

90% of

Set Point

[AtSP]

Default Setting

Auto-tuning at a Set Point of 200

°

F

Time

Chapter 7 Tuning, Manual
Operation, Alarms and Error
Codes