Silencing 4, Analog output, Sil4 – Watlow Series 998 User Manual
Page 57: Aout, Setup-output
WATLOW Series 998 User’s Manual
4.29
Setup Menus, Chapter 4
Setup-Output
Silencing 4
Select silencing to inhibit alarm 4 on startup and to allow the opera-
tor to reset the alarm output, not the visual display.
• Silencing disables the alarm until the signal is between [A4LO] and
[A4HI].
[SIL4] This prompt appears only on controllers equipped with output 4
hardware for a relay (99__ - ____ - _B__, or 99__ - ____ - _D__, or 99__ - ____
- _E__ or 99__ - ____ - _K__), or switched dc (99__ - ____ - _C__) and with
[`Ot4] set to [`AL4] or [AL4n].
Default
↓
[`OFF]
[``On]
[SIL4]
[SIL4]
Analog Output
Select which value to retransmit as the output 3 signal.
• [PrcA] retransmits the channel A input value.
• [SP`A] retransmits the set point for channel A.
• [Prcb] retransmits the channel B input value. This prompt appears only
if [`In2] is not set to [``no].
• [SP`b] retransmits the set point for channel B.
• [``no] turns off the retransmit function.
[Aout] This prompt appears only on controllers equipped with output 3
retransmit hardware (99__ - ____ - M___ or 99__ - ____ - N___).
Default
↓
[PrcA]
[SP`A]
[Prcb]
[SP`b]
[``no]
[Aout]
[Aout]
[Aout]
[Aout]
[Aout]
[SIL4]
NOTE:
See Chapter 7 for
more information on
alarms.
[Aout]
NOTE:
See Chapter 8 for
more information on
retransmit.