beautypg.com

Silencing 4, Analog output, Sil4 – Watlow Series 998 User Manual

Page 57: Aout, Setup-output

background image

WATLOW Series 998 User’s Manual

4.29

Setup Menus, Chapter 4

Setup-Output

Silencing 4

Select silencing to inhibit alarm 4 on startup and to allow the opera-
tor to reset the alarm output, not the visual display.

• Silencing disables the alarm until the signal is between [A4LO] and

[A4HI].

[SIL4] This prompt appears only on controllers equipped with output 4
hardware for a relay (99__ - ____ - _B__, or 99__ - ____ - _D__, or 99__ - ____
- _E__ or 99__ - ____ - _K__), or switched dc (99__ - ____ - _C__) and with
[`Ot4] set to [`AL4] or [AL4n].

Default

[`OFF]

[``On]

[SIL4]

[SIL4]

Analog Output

Select which value to retransmit as the output 3 signal.

• [PrcA] retransmits the channel A input value.

• [SP`A] retransmits the set point for channel A.

• [Prcb] retransmits the channel B input value. This prompt appears only

if [`In2] is not set to [``no].

• [SP`b] retransmits the set point for channel B.

• [``no] turns off the retransmit function.

[Aout] This prompt appears only on controllers equipped with output 3
retransmit hardware (99__ - ____ - M___ or 99__ - ____ - N___).

Default

[PrcA]

[SP`A]

[Prcb]

[SP`b]

[``no]

[Aout]

[Aout]

[Aout]

[Aout]

[Aout]

[SIL4]

NOTE:
See Chapter 7 for
more information on
alarms.

[Aout]

NOTE:
See Chapter 8 for
more information on
retransmit.