Software filter 2, Linearization 2, Altitude compensation – Watlow Series 998 User Manual
Page 42: Alt] [lin2] [ftr2, Setup-input
Setup Menus, Chapter 4
Setup-Input
Software Filter 2
Select the filter time constant, in seconds, for channel B. This
smooths a rapidly changing input signal for display or control purposes.
• Select a positive value to filter only the display.
• Select a negative value to filter the input signal.
• Set the value to [```0] to disable the filter.
[Ftr2] This prompts appears only if [`In2] is not set to [``no].
Default
↓
[`-60]
…
[```0]
…
[``60]
[Ftr2]
[Ftr2]
[Ftr2]
Linearization 2
Set the type of relative humidity sensor being used.
• Select [`30C] to provide temperature compensation when using the
Vaisala HMM-30C humidity sensor.
• Select [H260] to provide temperature compensation when using the
Rotronic H260 humidity sensor.
• Select [`Wb] when using a wet bulb/dry bulb sensor.
[Lin2] This prompt appears only if [`In2] is not set to [``no].
Default
↓
[`30C]
[H260]
[`Wb]
[``no]
[Lin2]
[Lin2]
[Lin2]
[Lin2]
Altitude Compensation
Set barometric correction for altitude above sea level.
[`Alt] This prompt appears only if [Lin2] is set to [`Wb].
Default
↓
[```0]
[2500]
[5000]
feet
[`ALt]
[`ALt]
[`ALt]
[`ALT]
[Lin2]
[Ftr2]
4.14
WATLOW Series 998 User’s Manual