Output prompts, Output 1a, Ot1a – Watlow Series 998 User Manual
Page 45: Setup-output
WATLOW Series 998 User’s Manual
4.17
Setup Menus, Chapter 4
Setup-Output
Output Prompts
When you are in the Setup menus, the Series 998 displays the menu
selection ( [InPt], [OtPt], [GLbL] or [COM] ) in the upper display, and
[`SEt] in the lower display.
The Up-arrow > or Down-arrow < key selects another menu. Press the
Mode key µ to display the first prompt in the lower display and its value
in the upper display. Use the Up-arrow or Down-arrow key to change the
value in the upper display. The new value will not take effect until after a
five-second delay or until you press the Mode key.
Output 1A
Set the way that output 1A will respond to a difference between the
set point and an input variable.
• [``Ht] select reverse action, so that output 1A responds when the input
signal is less than the set point.
• [``CL] select direct action, so that output 1A responds when the input
signal is more than the set point.
[Ot1A] This prompt always appears.
Default
↓
[``Ht]
[``CL]
[``no]
[Ot1A]
[Ot1A]
[Ot1A]
NOTE:
Decimal points may
not always be in the
position specified
below, depending
on the the setting of
Decimal 1
[deC1]
in
the Input Menu.
[Ot1A]