Output 4 wiring, 13 output 4 wiring, Ac outputs – Watlow Series 998 User Manual

Page 25: Switched dc, open collector, External transmitter power supply

background image

WATLOW Series 998 User’s Manual

2.13

Installation and Wiring, Chapter 2

Output 4 Wiring

Figure 2.13a

— AC Outputs

• Solid-state Relay with

Contact Suppression
0.5 Amps
Off-state impedance: 20K

min.

99 _ _ - _ _ _ _ - _ B _ _

• Solid-state Relay without

Contact Suppression
0.5 Amps
Off-state impedance: 31M

99 _ _ - _ _ _ _ - _ K _ _

Figure 2.13b

— Switched DC, Open Collector

Minimum load resistance: 500

99 _ _ - _ _ _ _ - _ C _ _

Figure 2.13c

— External Transmitter Power Supply

99 _ _ - _ _ _ _ - _ T _ _

See Chapter 1 for DIP switch location and settings.

For data communications wiring refer to How to Use
Data Communications with the Watlow Series 988 Family Controls.

NOTE:
Input-to-output iso-
lation is defeated
when the external
transmitter power
supply is used to
power a transmitter
connected to input
1 or input 2.

• Electromechanical Relay with

Contact Suppression
(On NO and COM contacts only)
Form C, 5 Amps
Off-state impedance: 20K

min.

99 _ _ - _ _ _ _ - _ D _ _

• Electromechanical Relay with-

out

Contact Suppression
Form C, 5 Amps
Off-state impedance: 31M

99 _ _ - _ _ _ _ - _ E _ _

External

Load

COM

L1

L2

Fuse

NO

5

6

NC

(7 for D & E outputs only)

7

5

External

Load

6

+

+ V

Î

Internal Circuitry

5

6

7

790

19 to 32V

Î

(dc)

7

-

COM

5

6

+

-

+V

-V

Transmitter

4-20mA out

Input

1 or 2

+

-