Error Code Actions

Error codes [`Er3], [`Er4], [`Er5] or [`Er9] will result in these con-
ditions

• The control is in Auto operation with both control outputs off.

• The alarm outputs are in their alarm state (de-energerzed with the indi-

cator light on).

• The lower display is blank.

• The upper display indicates the error code.

• All keys are inactive.

• [`Er5] resets all Setup Menu prompts to their default values.

• The above conditions occur regardless of the value of [FAIL] or the

presence of the Setup or Factory menus

Cycle power to the control. If the error is still present contact the factory.

Percent Output Level with [FAIL] not set to [bPLS]

Heat

Cool

[FAIL] set 1% to 100%

[FAIL] setting 0%

[FAIL] set -100% to -1%

0%

[FAIL] setting

Error Codes

WATLOW Series 998 User’s Manual

7.7

Tuning, Alarms and Error Codes, Chapter 7

Error codes other than [`Er3], [`Er4], [`Er5] or [`Er9] will result in
these conditions:

• If [FAIL] is set to [bPLS] (Global Menu)...

...and the control was in auto operation when the error occurred, it goes

into manual (% power) operation. If the output power is less than 75%
(±5%) power, and there was a change in power (< 5%) within the last
two minutes, the 998 switches into manual operation at the last auto-
matic power level (bumpless transfer). If the control was in manual
operation, it remains there. (Press the Auto/Man key å once to see
the error code.) The error code is shown in the upper display for five
seconds and the lower display shows the % power. After five seconds
the upper display reverts to the [----] display.

If the control was operating with stable output values when the error

occurred, it continues to operate at those levels on a % power basis. If
output values were not stable,or the percent output was greater than
75%, the control outputs go to 0% power (off).

• If [FAIL] is not set to [bPLS] (Global Menu)...

...and the control was in auto operation when the error occurred, it goes

into manual (% power) operation. The power level is determined by the
[FAIL] value (-100 to 100%). See the table.