4.9

Setup Menus, Chapter 4

RTD Calibration Curve 1

Select the calibration curve for the channel A RTD. The RTD input
uses either the European (DIN, 0.003850

/

/°C) or the Japanese (JIS,

0.003916

/

/°C) linearization standard.

[rtd1] This prompt appears only if you have set [`In1] to [`rtd] or
[`r†d].

Default

[`din]

[`JIS]

[rtd1]

[rtd1]

Software Filter 1

Select the filter time constant, in seconds, for channel A. This
smooths a rapidly changing input signal for display or control purposes.

• Select a positive value to filter only the display.

• Select a negative value to filter the input signal.

• Set the value to [```0] to disable the filter.

[Ftr1] This prompt always appears.

Default

[`-60]

[```0]

[``60]

[Ftr1]

[Ftr1]

[Ftr1]

Setup-Input

[rtd1]

[Ftr1]