beautypg.com

Channel b input wiring, Thermocouple, Rtd, 2- or 3-wire – Watlow Series 998 User Manual

Page 21

background image

WATLOW Series 998 User’s Manual

2.9

Installation and Wiring, Chapter 2

Channel B Input Wiring

Figure 2.9a

— Thermocouple

Thermocouple only
99 _ _ - _ 1 _ _ - _ _ _ _

Universal signal conditioner
99 _ _ - _ 2 _ _ - _ _ _ _

Figure 2.9b

— RTD, 2- or 3-wire

99 _ _ - _ 2 _ _ - _ _ _ _

Figure 2.9c

— 0-5V

О

О

, 1-5V

О

О

, 0-10V

О

О

(dc) Process

99 _ _ - _ 2 _ _ - _ _ _ _

Input impedance: 10K

Figure 2.9d

— 0-20mA or 4-20mA Process

99 _ _ - _ 2 _ _ - _ _ _ _

Input impedance: 7

NOTE:
Model number
99_ _-_ 1 _ _-_ _ _ _
has no In1 DIP
switch.

19

20

+

-

19

20

18

S2

S1

Jumper

19 to 20

for 2-wire

RTD

19

20

18

S2

S1

S3

20

18

-

+

m

A

20

19

-

+

V

DC

NOTE:
Using a grounded
thermocouple for
both input 1 and
input 2 can cause
ground loop prob-
lems.

O
N

1

2

3

O
N

1

2

3

J, K, T, N, C, E, Pt2, D
Dip Switch Setting

R, S, B
Dip Switch Setting

O
N

1

2

3

Dip Switch Setting

O
N

1

2

3

Dip Switch Setting

O
N

1

2

3

Dip Switch Setting

ç

CAUTION:
An external resistor
is required for
0-20mA and 4-20mA
process wiring to
prevent a high in-
rush current which
could burn out the
controller’s 7-ohm
resistor. See page
2.4. for recommen-
dations.