WATLOW Series 998 User’s Manual

4.13

Setup Menus, Chapter 4

Calibration Offset 2

Offset the channel B signal by a positive or negative value. This allows
you to compensate for lead resistance, sensor errors or other factors.

[CAL2] This prompt appears only if [`In2] is not set to [``no].

If

Default

[``°F]

[-999]

[```0]

[`999]

[`C_F]

[CAL2]

[CAL2]

[CAL2]

(Global Menu)

[``°F]

&

[`r†d]

[-9(9]

[``)0]

[`9(9]

[`C_F]

[`In2]

[CAL2]

[CAL2]

[CAL2]

(Global Menu)

(Input Menu)

[``°C]

[-555]

[```0]

[`555]

[`C_F]

[CAL2]

[CAL2]

[CAL2]

(Global Menu)

[``°C]

&

[`r†d]

[-5%5]

[``)0]

[`5%5]

[`C_F]

[`In2]

[CAL2]

[CAL2]

[CAL2]

(Global Menu)

(Input Menu)

[-999]

[```0]

[`999]

units

a process input

[CAL2]

[CAL2]

[CAL2]

is selected

RTD Calibration Curve 2

Select the calibration curve for the channel B RTD 2 input. The RTD
input uses either the European (DIN, 0.003850

/

/°C) or the Japanese

(JIS, 0.003916

/

/°C) linearization standard.

[rtd2] This prompt appears only if you have set [`In2] to [`rtd] or
[`r†d].

Default

[`din]

[`JIS]

[rtd2]

[rtd2]

Setup-Input

[CAL2]

[rtd2]